LIEBERT GXT5 EBC36VRT2U UPS BATTERY CABINET 36V DC OUTPUT

How to connect DC battery cabinet
Always connect the two DC lines between the battery management system and battery modules first. Always replace damaged battery modules without delay. Plug a connector of the supplied black DC cable from the APU connector set into the BATTERY- socket on the battery management system. [pdf]FAQS about How to connect DC battery cabinet
How do I connect a battery cabinet to an ups?
Connect the DC+ and DC- cables to the DC+ and DC- terminals. Connect the power cables in the UPS. If more battery cabinets are part of the solution, connect all battery cabinets to the UPS according to the diagram below.
How do I connect a DC+ & DC- cable?
Connect the DC+ and DC- cables to the DC+ and DC- terminals. Connect the PE cable to the PE terminal/Connect the EGC cable to the grounding terminal. For installations with two hole cable lugs only, temporarily remove the protection cover. NOTE: The protection cover must be reinstalled when the DC- cable has been connected.
Do I need a pull box with a Battery breaker?
NOTE: If the combined short circuit current of the battery cabinets exceeds the short circuit rating of the UPS, a pull box with fuses or an external box with a battery breaker must be installed. Please contact Schneider Electric for more information and refer to the submittal drawings for your specific UPS.

DC battery cabinet dimensions
Minimum cabinet height = Rack height (to top of rail) + Battery height + Space above battery (12" ideal) + Charger height + 6" (for space above charger) Chargers need room to breathe and batteries need extra room above for maintenance (watering and testing). [pdf]